Concepts

Process image

The engine owns one value per signal, the process image. Every value lives in a typed buffer sized at init and never resized. Connectors write inputs and tunables and read outputs from their own threads; the cycle thread copies what it needs at its tick and stores outputs back. Each signal is locked only for one copy.

A signal has a direction:

directionwritten byread by
inputa connectorthe instances that consume it
outputthe instance that produces itconnectors, other instances
tunablea connector, while runningone instance, before its step
systemthe engineconnectors

Element types are f64, f32, i64, i32, i16, i8, u64, u32, u16, u8 and bool. A signal is a scalar or an array of any rank; matrices are stored row-major or column-major as the model declares.

Ticks and periods

One real-time thread wakes on an absolute deadline grid (clock_nanosleep with TIMER_ABSTIME) every engine.tick_ms. Each instance has a period of every ticks and is due at every tick whose number is a multiple of every, so all instances are due at tick 0.

Per tick:

  1. The external inputs and tunables of every due instance are copied from the image.
  2. If any of those inputs is stale, the tick is skipped (see stale inputs).
  3. Otherwise the due instances step in declared order. Each first copies its wired inputs, so it sees outputs stored earlier in the same tick.
  4. Outputs are stored, the heartbeat advances and the tick is published: connectors now see a complete, consistent set of outputs.

Model time is start_time + tick × tick_ms; an instance advances by its step size every × tick_ms per step. A tick that ends after the next deadline skips the missed slots and counts each in overruns; the tick counter stays contiguous, so after an overrun model time lags wall time by the skipped slots. Nothing on the tick path allocates.

Instances and dimensions

A model is size-generic: its variables have symbolic shapes (u: f64[n], A: f64[nx, nx]) over named dimensions with an optional min, max and default. An instance references a model and binds every dimension, from the project file, from the model’s default, or "from-server" (the length a connector finds outside). The bound sizes are structural: they are fixed for the run, and a change needs a restart.

One model serves any number of instances. Whether one loaded library can host several is the model’s instances capability: multiple libraries keep their state per instance; for a single library (state in globals), each further instance loads a private copy of the file.

Parameters are set once before init. Tunables are set before init and change while running; a changed value is delivered before the instance’s next step. A tunable that no connector has written yet shows the model’s own start value after init, so writing one tunable never zeroes another.

Signals and wiring

An unmapped input, output or tunable v of instance i is the signal i.v. Mapping a variable in the project file names its signal:

  • An input mapped to a signal that some instance outputs is wired to it. It reads what the producer stored last: the same tick when the producer runs earlier in declared order, else the previous one. A wired input never goes stale.
  • An input nobody outputs is an external input, written by a connector.
  • Several instances may consume one signal.
  • A one-dimensional input may be composed element by element from scalar signals and elements of other instances’ outputs, each element wired or external as above; its value is the read-only signal i.v. A scalar input may take one element, x = "j.y[2]", the same way. See Project file.

Errors at init: two outputs on one signal, a tunable on an input or output signal, one signal used with two types, shapes or layouts, a mapping onto one of the engine’s own signals, or a signal name with [ or ] that is no element of another instance’s output.

Init

Before the first tick every instance is initialised once, in declared order. Its init sees its dimension lengths and parameters, its tunables as the image holds them (a connector’s write, else the start value), and its inputs as follows:

  • A wired input whose producer comes earlier in declared order holds the producer’s output as it stood after the producer’s init, so a library may seed its state from it.
  • A wired input whose producer comes later (a feedback loop) is zero.
  • An external input holds what a connector has written so far, zero if nothing yet. No first read is awaited and no age limit is checked at init.
  • The elements of a composed input follow the same rules, element by element.

Outputs written by an init are not stored in the image: connectors and other instances see outputs from tick 0 on, and every wired input is copied again before each step.

Stale inputs

Each external input may carry a maximum age, max_age_ms on the binding or engine.input_max_age_ms for all. Without one, an input never goes stale. With one, an input is stale when its last write is older than that at the tick, or when it was never written.

A stale input skips the whole tick: no instance steps, outputs and heartbeat are held, status becomes faulted and stale counts the tick. The fault is published at once. When inputs are fresh again the next tick runs normally and status returns to running.

An OPC UA client connector that loses its server stops writing its inputs, so they age and the engine turns them stale.

Heartbeat, status and the safety contract

The engine publishes its own signals under engine.system_prefix (default taktwerk):

signaltypemeaning
taktwerk.heartbeatu64advances once per tick whose outputs were published
taktwerk.statusi320 init, 1 running, 2 faulted, 3 stopped
taktwerk.cycleu64every tick, skipped ones included
taktwerk.overrunsu64deadline slots missed
taktwerk.staleu64ticks skipped for a stale input

Models run inside the engine’s process; there is no process isolation. Whoever consumes the outputs, typically the PLC, owns the safe state. It watches the heartbeat (map it to a PLC node with the OPC UA client) and falls back to its safe state when the heartbeat stops advancing or status is not 1. The heartbeat advances only on a tick whose outputs were published, so a held heartbeat means the outputs are not current.

Fail-stop

A model error (a non-success return code, or a failed init) terminates every instance and ends the run with that error; taktwerk run exits non-zero. A connector that fails beyond its own reconnect logic stops the run the same way. The engine does not retry: restart is the service manager’s job (see Running in production).